6. System Start-up, Operation, and Maintenance

Bioreactors used to treat MIW are generally designed for minimum operational maintenance, especially when located in remote areas. For example installation in a remote area where maintenance is difficult or unlikely can result in failure to provide treatment (see Appendix B.14, Lady Leith mine case study).

However, some level of operational controls and maintenance are necessary to achieve the performance expectations of the bioreactor and treatment system as a whole.

This section describes the following monitoring, operation, and maintenance activities:

The monitoring section describes monitoring tools and techniques for the physical condition of the bioreactor, the system flow rate and water chemistry for operational performance, and water chemistry for regulatory compliance. The maintenance subsection includes substrateEither (a) a chemical which reacts or (b) a solid surface or (c) an electron donor./nutrient replacement, troubleshooting and preparation of an operation and maintenance plan.

6.1 System Start-up

Start-up should allow sufficient growth of the microbial populations to establish a stable biomass within the reactor unit. As described in Section 3, the source of the microbes often is from manure (Table 1-1), but may also come from any combination of laboratory designed inoculum, wastewater, anoxic site sediments, or source water (Gusek and Figueroa 2009; La et al. 2003; Perrault et al. 2009). Appropriate chemical and physical conditions are necessary to promote the growth of the desired microorganisms. The sulfate reducing bacteria require anoxic or very low dissolved oxygen levels, sulfate, and an organic carbon food source.

BCR Start-up

During a two week start-up, pumps recycled the water within the two BCR cells. Based on data collected in field, and subsequent laboratory confirmation, the water from the BCR cells was routed to the tailings pond for temporary storage and later treatment and release. At that point, the rock filter and aeration ponds were brought on-line. In the meantime, the mine discharged according to plan through an overflow pipe from the settling pond as it had during construction of the other components. See Appendix B.7 West Fork Mine Case Study for more details.

There are generally three phases of start-up:

  1. Reactor flooding
  2. Low-flow or recirculated flow operation
  3. Full-flow operation with frequent monitoring

To initiate the required conditions, system flooding allows the microbes to incubate. This flooding wets all the material in the treatment unit, and allows soluble carbon and sulfate to come into contact with the microbes thereby allowing establishment of attached microbial growth without washing food and microbes out of the reactor unit. During this flooded period microbes use oxygen in the influent water to consume organic carbon. These microbes may continue to be present in the system during normal operations and many aerobic microorganisms are facultative instead of obligate aerobic microorganisms.

6.2 Monitoring and Maintenance Activities

Biochemical reactor systems generally have a lower operation and maintenance requirements than traditional active treatment plants. However, a certain level of operations, monitoring, and maintenance is required. The level of effort required depends on many factors including chemical and hydraulic loading rates, variability of loading rates, design, location, and the degree of flexibility in the discharge criteria.

This section describes the operations and monitoring that should be considered for a biochemical reactor. The main objectives of operations and monitoring are to manage the system for smooth operation and minimal upsets and to determine compliance with target water quality criteria. To achieve smooth operation it is important to maintain flow and loading within the designed system limits and to regularly assess system conditions and performance as a predictor for potential upsets, necessary maintenance, decline in effectiveness over time, and end of useable life.

Three main types of monitoring to consider are as follows:

  1. monitoring the physical condition of the system
  2. operational performance monitoring of system flow rates and water chemistry conditions
  3. monitoring water chemistry for regulatory compliance

6.2.1 Monitoring the Physical Condition of the System        

Monitoring the physical condition of the system generally includes visual inspection of the overall system and site and the various components of the system, including pre- and post- treatment units. Observe changes from normal operations and track changes that may occur slowly over time in order to identify and mitigate minor problems before they cause major system upsets. Regular inspection should include monitoring flow through the system, system integrity, and site access.

6.2.2 Operational Performance Monitoring of Flow and Water Chemistry

Both influent and effluent flow rates and water chemistry monitoring are important to assess the operation of the biochemical reactor unit. Frequency, location, and water chemistry parameters suggested for monitoring are discussed in the following subsections. Table 6-1, Sample Locations, Frequency and Purpose of Sampling, summarizes the sampling locations, frequency and purpose of sampling.

6.2.2.1 Sampling Frequency

A monthly operational monitoring frequency has been established for several demonstration sites (Bless, et al. 2008). In some cases, monitoring is increased to once per week for field parameters and once per two weeks for laboratory analytical parameters in the summer months when remote sites are more accessible (see Appendix B.8 Leviathan Mine Case Study). Always be cautious about sample frequency through changing seasonal conditions and the effect these seasonal changes can have on a sample or on a site's accessibility for collecting samples.

6.2.2.2 Water Chemistry and Quality Parameters

Water chemistry parameters generally consist of those that can be measured in the field with probes, meters or colorimetric tests kits and those that require laboratory analysis.

Field parameters, their importance and their general purpose are listed below under required and optional categories. Required field parameters include the following:

6.2.2.3 Sampling Locations

The following locations are recommended for operational monitoring: (see Table 6-1)

In systems with redundant biochemical reactors or other redundant treatment units, the sampling locations described above should also be included for the redundant units.

6.2.3 Compliance Monitoring

How treatment discharge is regulated can vary widely depending on the regulatory agency, geographical location, and receiving water body, as well as if the site is an abandoned or active mine site. Generally it is assumed that biochemical reactor systems will discharge effluent to surface water rather than groundwater. Surface water discharges to streams, wetlands and oceans are typically regulated by the Clean Water Act of 1972 (CWA) or State or tribe equivalent. In most cases active mine sites must comply with provisions of the Surface Mining Control and Reclamation Act (SMCRA) for coal mining and hard rock mining and secure permits for discharges to surface waters under the National Pollutant Discharge Elimination System (NPDES). Allowable contaminant concentrations regulated by NPDES permits are determined by the US Environmental Protection Agency’s technology-based standards or toxicity-based standards established for stream uses, or the state or tribal equivalent. The permits are generally site-specific and may include total maximum daily loads (TMDL). Abandoned mine sites fall under other regulatory purviews including CERCLAComprehensive Environmental Response, Compensation and Liability Act, RCRAResource Conservation and Recovery Act, SMCRASurface Mining Control and Reclamation Act, brownfields, state, local, or tribal programs.   

6.3 Maintenance

6.3.1 Substrate Nutrient Change Out

6.3.2 Troubleshooting

Two main categories of troubleshooting exist: chemical trends and physical trends. Chemical trends involve: 1) increasing trends in the concentrations of Fe, Al, and Mn in the influent, 2) decrease of reduced sulfur/increase in sulfate in the effluent, 3) increase in BODbiological oxygen demand/CODchemical oxygen demand in the system effluent, and 4) change in Eh, pH in the reactor, and DOdissolved oxygen. Physical trends include plugging, loss of effluent, overflow of bioreactor or influent pond, short circuiting, and loss of structural integrity of berms, dikes, ponds, erosion, and storm water control features.

6.3.2.1 Field Data

This section provides “real time” guidance on BCR or system observations that may suggest potential performance problems that would be validated when results from analytical sampling are received (see Section 6.3.2.2). Each system is unique; the following discussion is focused on systems that are past the commissioning/start-up period and would be considered in “steady state” operation.

Note: some of the guidance provided may not apply in every situation; alternative configurations (such as upflow or horizontal flow) may create circumstances that are unique to a given site or system. The guidance is typically applicable for downflow/top-fed configured BCRs unless otherwise noted.

6.3.2.2 Chemical Trends

6.3.2.3 Physical trends

6.4 Sampling Protocol

Based on monitoring parameters described in Section 6.2, this section describes methods and equipment used to collect samples, and methods for in situ and laboratory analysis. Always check tribal, state, and federal rules for required or preferred sample collection and analytical methods.

6.4.1 Sample Collection

6.4.5 Sample transportation

Transport of sample containers must be made in insulated coolers containing ice or cooling material. It is worth mentioning that the use of foam will help in preventing ruptures. Containers should be kept cool, dark and in a vertical position. Upon arrival at the laboratory, a chain of custody form must be filled out by the analyst and samples should be checked according to the shipping list. Samples must be immediately stored at 4°C until analysis.

Maximum periods of storage and preservation methods prior to analysis are included in Table 6-3. In any case, it is recommended that the time interval between sample collection and analysis must be minimized.

Table 6-4. Sample collection details

Parameter

Container

Sample volume [mL]

Type of sample

Preservation method

Maximum storage time

pH

P, G

50

S

Analysis in situ

2 h

Temperature

P, G

--

S

Analysis in situ

Seconds

Conductivity

P, G

500

S, C

Cooled

48 h

Solids

P, G

200

S, C

Cooled

7 d

Bacteria

P, G

100

S

Cooled

24 h

BODbiological oxygen demand

P, G

1000

S

Cooled

48 h

CODchemical oxygen demand

P, G

500

S, C

Add H₂SO4 until pH 2 and cool

28 d

Mercury

Teflon

100

S, C

Add HNO₃ until pH 2 and cool

28 d

Dissolved metals

P(a), G(a)

500

S

Sample must be filtered in situ, add HNO₃ until pH 2, store and cool

6 m

Nitrates

P, G

100

S, C

Cooled

48 h

Nitrites

P, G

100

S, C

Add H₂SO4 until pH 2 and cool

48 h

Cyanide

P, G

500

S, C

Add NaOH until pH 12 and cool

24 h

P: Plastic; P(a): Plastic container previously washed with 1:1 HNO₃

G: Glass; G(a): Glass container previously washed with 1:1 HNO₃

S: Simple; C: Composite

h: hour; d: day; m: month

6.4.6 Field QA/QC

The USEPA (2002) guidance for use in developing a Quality Assurance Project Plan (QAPP) when designing an environmental data collection program is commonly used and accepted.

6.4.7 Laboratory QA/QC

In order to have a trustworthy result, the laboratory should follow adequate quality assurance/quality control standards, such as those listed in Laboratory Documentation Required For Data Evaluation (USEPA 2001). Additional information can be found in Hibbert (2007).

The following principles are important to consider when making reliable analytical measurements:

6.4.8 Flow Measurement Methods

Flow meters used to characterize the quantity of water, expressed as volume or mass per unit of time, are based on the fundamental equations of hydraulics (continuity equation), which are valid in open or pressure conduits:

Q = v · A

where:

Q = Volume (in units of volume/time, m3/s)

v = Velocity of fluid (in units of length/time, m/s)

A = Area through which the fluid has the velocity (v) (m2)

Flow is determined using devices or primary instruments that are calibrated hydraulic structures, installed at a driving point of the fluid. Measurements can be obtained by determining the physical variables at specific points in the structure.

It is common to use a secondary instrument to determine the actual flow passing through the point of measurement, that is, capture of the signal emitted by a primary instrument (sonic means, light, electronics) and convert that signal to hydraulic data (flow, velocity, pressure). Measuring instruments can be classified into two groups:

The most common method of measuring flows for pilot and full scale BCRs is in open channel or free surface flow. Flow freely exposed to atmospheric pressure, like canals can be measured from the hydraulic loads (head) across a defined structure (such as the Parshall flume, a venturi or orifice plate) and water velocity (as through a turnstile), or using thermal, magnetic, or sonic techniques.

Meters most commonly used for BCR influent, effluent and overflows in open channels are rectangular weirs, V weirs and Parshall flumes. These devices can measure flow rates of water containing a certain amount of suspended solids like those resulting from BCR treatment. (Appendix D)

6.5 Contents of an Operation and Maintenance Plan

An operation and maintenance plan (O&M Plan) should be sufficiently detailed such that a new owner/operator of the site can take over operations without encountering major gaps in understanding the bioreactor system function. The O & M Plan should include a narrative report that describes the following:

  1. The site background, location, and contact information
  2. A description of the treatment system, including schematic diagrams
  3. A description of flow measurement and water sampling locations and methods
  4. A description of routine and major maintenance activities

At least one schematic diagram of the treatment system should be provided, and more than one diagram is recommended to show detail. One of the schematics should be an aerial-view diagram (preferred scale: between 1 inch:50 feet and 1 inch:100 feet). The schematic(s) should include a legend and should clearly depict the following:

An example schematic diagram is shown in Figure 6-3.

Figure 6-3. Site treatment layout, example schematic.

Source: Modified from Western Pennsylvania Coalition for Abandoned Mine Reclamation, http://www.wpcamr.org/facts/groups/omr-plan/omr-schematic.pdf.

The site location should be depicted on a map and latitudinal and longitudinal coordinates should be provided, if available. Directions to the site should be provided, and the name, address and phone number of the operator should be available on site for issues regarding access and in case of emergency. Any hazards at the site should be clearly identified.

6.5.1 Site Background

6.5.2 Treatment System

6.5.3 Flow Measurement and Water Sampling

6.5.4 Maintenance Activities

6.5.5 Health and Safety

Every BCR system should have a site specific health and safety plan (HASP) that advises inspectors of the hazards of H₂S. Liability issues prevent ITRC from including a HASP in this guidance document. The HASP should be prepared by a licensed professional familiar with the hazards.

Publication Date: November 2013

Permission is granted to refer to or quote from this publication with the customary acknowledgment of the source (see suggested citation and disclaimer).

 

This web site is owned by ITRC.

1250 H Street, NW • Suite 850 • Washington, DC 20005

(202) 266-4933 • Email: [email protected]

Terms of Service, Privacy Policy, and Usage Policy

 

ITRC is sponsored by the Environmental Council of the States.